The maximum and minimum of the values measured since power application
or RESET signal input up to the present point are retained. When the RESET
signal turns ON, both the maximum and minimum values are reset to the
present value. Even though the maximum and minimum values are retained
in memory, the comparative output and BCD output are output in accordance
with changes in the measured value, regardless of the display or even if the
RESET signal is OFF, except as controlled by the HOLD input (see next fea-
ture).
Hold Measured Value
When the HOLD input is turned ON during RUN mode, measurement stops
and the input measured just before the HOLD input turned ON is held. The
displayed value, comparative output, BCD data, etc., are also held.
Test Mode
This function is convenient for checking a system to which the Intelligent Sig-
nal Processor is connected, especially when some inputs cannot be oper-
ated. The Intelligent Signal Processor simulates an input, changing the dis-
play and output conditions.
This function allows the measured values, comparative outputs, and linear
output range to be set as set values while actual measurement is being car-
ried out. This function is useful for setting parameters while checking the op-
erating status of the Intelligent Signal Processor.
Input Range
Input ranges of 4 to 20 mA, 1 to 5 V, or
±
9.999 VDC can be selected.
Maximum/Minimum Values
Teaching Function
Section 1
Summary of Contents for K3TS
Page 1: ...K3TS Intelligent Signal Processor Operation Manual Revised August 1997...
Page 2: ......
Page 4: ......
Page 5: ...0 1 2 3 4 5 0 5 2 0 4 6 7 89 6 9 0...
Page 6: ......
Page 8: ...9 1 4...
Page 11: ...1...
Page 16: ...1...
Page 20: ...1 1...
Page 22: ...1...
Page 24: ...1 1 1 91 0 8 91 8...
Page 68: ...1 1 0 1...
Page 73: ...1 6 2 3 4 5 0 5 2 0 4 6 7 89 6...
Page 85: ...6 1 5...
Page 96: ...2 2 324 4 4 72 70 4 0 2 0 2 0 324 5 6 324 4 3 324 5 6 324 4 3 72 0 2...