Simple I/O Allocation
Section 4-2
Note
1.
Individual bits will be enabled only through those for the maximum number
of connected Temperature Controllers set on the rear panel rotary switch.
2.
Words will be allocated only through those for the maximum number of
connected Temperature Controllers.
Example:
If the maximum number of connected Temperature Controllers is 10, then
the allocated IN Area will be the 36 words, i.e., from the first word to the
first word + 35 words.
Data Allocated in the
OUT Area
The following table shows the configuration of the OUT Area when simple I/O
allocation is used.
First word + 35 words
Unit 10, Ch2 PV (type number 100) (See note 2.)
First word + 36 words
Unit 11, Ch1 PV (type number 100) (See note 2.)
First word + 37 words
Unit 11, Ch2 PV (type number 100) (See note 2.)
First word + 38 words
Unit 12, Ch1 PV (type number 100) (See note 2.)
First word + 39 words
Unit 12, Ch2 PV (type number 100) (See note 2.)
First word + 40 words
Unit 13, Ch1 PV (type number 100) (See note 2.)
First word + 41 words
Unit 13, Ch2 PV (type number 100) (See note 2.)
First word + 42 words
Unit 14, Ch1 PV (type number 100) (See note 2.)
First word + 43 words
Unit 14, Ch2 PV (type number 100) (See note 2.)
First word + 44 words
Unit 15, Ch1 PV (type number 100) (See note 2.)
First word + 45 words
Unit 15, Ch2 PV (type number 100) (See note 2.)
Address
Item
Address
Item
First word + 0 words
Output Enable Bits Units 0 to 7 (See note 1.)
First word + 1 words
Output Enable Bits Units 8 to 15 (See note 1.)
First word + 2 words
RUN/STOP Units 0 to 7 (See note 1.)
First word + 3 words
RUN/STOP Units 8 to 15 (See note 1.)
First word + 4 words
AT execute/cancel Units 0 to 7 (See note 1.)
First word + 5 words
AT execute/cancel Units 8 to 15 (See note 1.)
First word + 6 words
Unit 0, Ch1 SP (type number 123) (See note 2.)
First word + 7 words
Unit 0, Ch2 SP (type number 123) (See note 2.)
First word + 8 words
Unit 1, Ch1 SP (type number 123) (See note 2.)
First word + 9 words
Unit 1, Ch2 SP (type number 123) (See note 2.)
First word + 10 words
Unit 2, Ch1 SP (type number 123) (See note 2.)
First word + 11 words
Unit 2, Ch2 SP (type number 123) (See note 2.)
First word + 12 words
Unit 3, Ch1 SP (type number 123) (See note 2.)
First word + 13 words
Unit 3, Ch2 SP (type number 123) (See note 2.)
First word + 14 words
Unit 4, Ch1 SP (type number 123) (See note 2.)
First word + 15 words
Unit 4, Ch2 SP (type number 123) (See note 2.)
First word + 16 words
Unit 5, Ch1 SP (type number 123) (See note 2.)
First word + 17 words
Unit 5, Ch2 SP (type number 123) (See note 2.)
First word + 18 words
Unit 6, Ch1 SP (type number 123) (See note 2.)
First word + 19 words
Unit 6, Ch2 SP (type number 123) (See note 2.)
First word + 20 words
Unit 7, Ch1 SP (type number 123) (See note 2.)
First word + 21 words
Unit 7, Ch2 SP (type number 123) (See note 2.)
First word + 22 words
Unit 8, Ch1 SP (type number 123) (See note 2.)
First word + 23 words
Unit 8, Ch2 SP (type number 123) (See note 2.)
First word + 24 words
Unit 9, Ch1 SP (type number 123) (See note 2.)
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...