106
Sending Explicit Messages
Section 6-5
6-5-4
Setting and Monitoring Temperature Controller Channels
Note The following table shows the relationship between the Instance IDs (01 to 31)
and the Temperature Controller unit numbers (0 to 15) and channels (1 and
2).
Explicit
message
Read
/write
Function
Command
Response
Service
code
Class ID Instance
ID
Attribute
ID
Data size
Tempera-
ture Con-
troller
Channel
Mainte-
nance Infor-
mation
Monitor
Mode
Read Reads the monitor
mode for maintenance
information of the Tem-
perature Controller unit
number and channel
(see note 1) specified
by the Instance ID (1 to
32).
0E hex
7A hex
01 to 20
hex
65 hex
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
Write
Writes the monitor
mode for maintenance
information of the Tem-
perature Controller unit
number and channel
(see note 1) specified
by the Instance ID (1 to
32).
10 hex
7A hex
01 to 20
hex
65 hex
1 byte
00 hex: Unit
conduction
time mode
01 hex: Total
RUN time
mode
Set Value
for Unit
Conduction
Time or
Total RUN
Time
Read Reads the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
0E hex
7A hex
01 to 20
hex
68 hex
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Write
Writes the set value
(monitor value) for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
10 hex
7A hex
01 to 20
hex
68 hex
4 bytes
00000000 to
FFFFFFFF
hex (0 to
4294967295)
Unit Con-
duction
Time or
Total RUN
Time Read
Read Reads the PV for the
Unit conduction time or
total RUN time (unit: s)
of the Temperature
Controller unit number
and channel (see note
1) specified by the
Instance ID (1 to 32).
0E hex
7A hex
01 to 20
hex
66 hex
4 bytes
00000000 to
FFFFFFFF hex
(0 to
4294967295)
Monitor
Status of
Unit Con-
duction
Time or
Total RUN
Time Read
Read Reads the monitor sta-
tus for the Unit conduc-
tion time or total RUN
time (unit: s) of the
Temperature Control-
ler unit number and
channel (see note 1)
specified by the
Instance ID (1 to 32).
0E hex
7A hex
01 to 20
hex
67 hex
1 byte
00 hex: Within
range
01 hex: Out of
range (monitor
value
exceeded)
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...