96
Sending CompoWay/F Commands to a Temperature Controller
Section 6-2
Command Block
Note Note: For broadcasting, specify XX (58 hex 58 hex ASCII)
Example: Unit number = 01, FINS-mini command text = 01 01 C0 0000 00
0001 (Executes Read from Variable Area (01 01), to read one element for ch1
PV (C0 0000).)
Response Block
Normal Response
6-2-3
List of FINS-mini Commands
The following table lists the FINS-mini commands that can be sent to the Tem-
perature Controllers. For details on commands and the variable area, refer to
the E5ZN Temperature Controller Operation Manual (H113).
Class ID
Instance ID
Data (CompoWay/F command frame data)
0086 hex fixed
0001 hex fixed
1 byte
1 byte
2 bytes
2 bytes
FINS-mini command text
Sub-address
SID
Destina-
tion
node
address
Service
Code
37 hex
fixed
Specified in ASCII code
(See following example.)
Unit No.
(See note.)
[00]= 3030
hex fixed
[0]= 30
hex
fixed
Unit No.
Sub-address
SID
FINS-mini command text
30 hex
31 hex
30 hex
30 hex
30 hex
30 hex
30 hex
31 hex
30 hex
31 hex
43 hex
30 hex
FINS-mini command text
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
30 hex
31 hex
Data (CompoWay/F response frame data)
Returns in ASCII code
2 bytes
1 byte 1 byte
Unit No.
Sub-address
End code
FINS-mini response text
No. of receive
bytes
Source
node
address
Service
Code
B7 Hex
fixed
[00]=
3030 Hex
fixed
MRC
SRC
Service name
Description
MRC, SRC notation
CompoWay/F
binary
commands
CompoWay/F ASCII
commands
01
01
Read from vari-
able Area
Reads from the variable area.
01 hex 01 hex
30 hex 31 hex 30 hex 31 hex
01
02
Write to Variable
Area
Writes to the variable area.
01 hex 02 hex
30 hex 31 hex 30 hex 32 hex
01
04
Read from Multiple
Variable Area
Performs non-consecutive multiple
reads from the variable area.
01 hex 04 hex
30 hex 31 hex 30 hex 34 hex
01
13
Write to Multiple
Variable Area
Performs non-consecutive multiple
writes to the variable area.
01 hex 13 hex
30 hex 31 hex 31 hex 33 hex
05
03
Read Controller
Attribute (See note
1.)
Reads information, such as the
model number.
Not used.
30 hex 35 hex 30 hex 33 hex
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...