74
Operations from the Edit Device Parameters Window
Section 5-2
Setting Method
1,2,3...
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the General Tab, and enter the desired value in the Network
Power Voltage field.
5-2-5
Setting the Unit Conduction Time Monitor
The DeviceNet Communications Unit can record the conduction time (time
that communications power is supplied to the Unit), and when the value
exceeds the set monitor value, the Unit Maintenance Bit in the Unit Status
Area will be turned ON.
This function provides a guideline for when to replace the Unit.
Measuring unit: 0.1 h
Measured time: 0 to 429496729.5 h
(stored data: 00000000 to FFFFFFFF hex)
Monitor value setting range: 0 to 429496729 hours (specify as an integer)
The present value for conduction time and the Unit Status Area can be
checked in the Maintenance Information Window when using Maintenance
Mode.
Note The present value and monitor value for the conduction time are held even
when the power is turned OFF.
Setting Method
1,2,3...
Open the Edit Device Parameters Window for the DeviceNet Communications
Unit, select the General Tab, and enter the desired value in the Unit Conduc-
tion Time field.
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...