![background image](http://html1.mh-extra.com/html/omron/e5zn-drt/e5zn-drt_operation-manual_742104113.webp)
98
Examples Using CompoWay/F Commands
Section 6-3
Command Details
[CMND S D C]
Response (Operation1)
S
0: 2801 hex
Command code
+1: 0036 hex
DeviceNet Communications Unit node address = 00
Service code = 36 hex
+2: 0086 hex
Class ID = 0086 hex
+3: 0001 hex
Instance ID = 01 hex
+4: 0000 hex
E5ZN unit number = 00 hex, sub-address (fixed) =
00 hex
+5: 0001 hex
SID (fixed) = 00 hex MRC = 01 Hex
+6: 02C1 hex
SRC = 02 hex, variable type = C1 hex
+7: 0003 hex
Write start address = 0003 hex (2 bytes)
+8: 0000 hex
Bit position (fixed) = 00 hex, No. of elements = 00
hex (2 bytes)
+9: 0100 hex
No. of elements = 01 hex, Data = 00 hex (4 bytes)
+10: 0002 hex
Data = 0002 hex
+11: 4000 hex
Data = 40 hex
D
D01200:
First response storage word
C
0: 0017 hex
No. of command data bytes
+1: 0010 hex
No. of response data bytes
+2: 0000 hex
Remote (destination) network address = 0
+3: 3FFE hex
Remote (destination) node address = 3F hex
Remote (destination) Unit address = FE hex (10 hex
also possible)
+4: 0000 hex
Response required, communications port No.0, No.
of retries = 0 hex
+5: 0064 hex
Response monitoring time
0: 2801 hex
Command code
+1: 0000 hex
End code (FINS)
+2: 0009 hex
No. of bytes received
+3: 00B6 hex
Node address = 00 hex, Service code = B6 hex
+4: 0000 hex
E5ZN unit number = 00 hex, Sub-address (fixed) = 00 hex
+5: 0001 hex
End code (CompoWay/F) = 00 hex, MRC = 01 hex
+6: 0200 hex
SRC = 02 hex, End code (FINS-mini) = 00 hex (2 bytes)
+7: 0000 hex
End code (FINS-mini) = 00 hex
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...