Operations from the Edit Device Parameters Window
Section 5-2
5-2
Operations from the Edit Device Parameters Window
5-2-1
Preparing the Configurator Connection
If problems occur in the connection with the Configurator, change the settings
for the master. Problems will occur if the master’s message timeout time is too
short or the I/O size allocated in the master is different from that allocated in
the DeviceNet Communications Unit.
Configurator Connected Using a DeviceNet Interface Board (Card)
1,2,3...
1.
Right-click the icon for the master, then select Monitor to display the Mon-
itor Device Window.
2.
Click the Stop Remote I/O Communication Button to stop remote I/O
communications with the DeviceNet Communications Unit.
Note This operation is not required if no error has occurred in the master node.
Master Connected using Serial Line
1,2,3...
1.
Double-click the icon for the master to display the Edit Device Parameters
Window and click the Message Timer Tab.
2.
Double-click the unit number of the DeviceNet Communications Unit, set
5,000 ms in the Setup Message Timer Window, and execute download.
5-2-2
Edit Device Parameters Window
1,2,3...
1.
Turn ON the power to the DeviceNet Communications Unit and master,
and then put the Configurator online, and select Upload from the Network
Menu.
The configuration of Units connected in the Network will be read and dis-
played in the Network Configuration Window.
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...