51
Allocating I/O from the Configurator
Section 4-3
Note The data in the Temperature Controller variable area is expressed in 8-digit
hexadecimal, but the allocation data is expressed in 4-digit hexadecimal. Vari-
ables other than statuses actually use the leftmost 4 digits only, so they can
be used without difficulty. When the Temperature Controller manuals are used
for reference, add 0000 (or FFFF for negative numbers) to the beginning of
numeric values.
Statuses are handled as 8-digit hex a decimals, so the leftmost 4 digits (bits 0
to 15) of allocated data is referred to as Status A and the rightmost 4 digits
(bits 16 to 31) as Status B.
Operation Monitoring Data (Correspond to Variable Type C0)
Operation Parameters (Correspond to Variable Type C1)
Allocated
in IN
Area
Allocated
in OUT
Area
Type
number
Data name
Temperature
Controllers that
support setting
Temperature Controller variable area
address
Pulse
output
type
Analog
output
type
ch1
ch2
Variable
type
Address Variable
type
Address
Yes
No
100
PV
Yes
Yes
C0
0000
C0
0100
Yes
No
101
Status A (rightmost
16 bits)
Yes
Yes
C0
0001
C0
0101
Yes
No
102
Status B (leftmost 16
bits)
Yes
Yes
C0
0001
C0
0101
Yes
No
103
Internal SP
Yes
Yes
C0
0002
C0
0102
Yes
No
104
Heater current value
monitor
Yes
No
C0
0003
C0
0103
Yes
No
105
MV monitor for heat-
ing
Yes
Yes
C0
0004
C0
0104
Yes
No
106
MV monitor for cool-
ing
Yes
Yes
C0
0005
C0
0105
Yes
No
107
PV hold value
Yes
Yes
C0
0006
C0
0106
Allocated
in IN
Area
Allocated
in OUT
Area
Type
number
Data name
Temperature
Controllers that
support setting
Temperature Controller variable area
address
Pulse
output
type
Analog
output
type
ch1
ch2
Variable
type
Address Variable
type
Address
No
No
120
Operation/adjust-
ment protection
Yes
Yes
C1
0000
C1
0100
No
No
121
Initial setting/com-
munications protec-
tion
Yes
Yes
C1
0001
C1
0101
No
No
122
Setting change pro-
tection
Yes
Yes
C1
0002
C1
0102
Yes
Yes
123
SP
Yes
Yes
C1
0003
C1
0103
Yes
Yes
124
Alarm value 1
Yes
Yes
C1
0004
C1
0104
Yes
Yes
125
Alarm upper limit
value 1
Yes
Yes
C1
0005
C1
0105
Yes
Yes
126
Alarm lower limit
value 1
Yes
Yes
C1
0006
C1
0106
Yes
Yes
127
Alarm value 2
Yes
Yes
C1
0007
C1
0107
Yes
Yes
128
Alarm upper limit
value 2
Yes
Yes
C1
0008
C1
0108
Yes
Yes
129
Alarm lower limit
value 2
Yes
Yes
C1
0009
C1
0109
Summary of Contents for E5ZN-DRT
Page 3: ...iv ...
Page 5: ...vi ...
Page 9: ...x ...
Page 15: ...xvi EC Directives 6 ...
Page 83: ...68 Ladder Programming Examples Section 4 5 ...
Page 123: ...108 Sending Explicit Messages Section 6 5 ...
Page 135: ...120 Message Communications Characteristics Section 7 2 ...
Page 157: ...142 Index Unit status 57 85 user set allocations 43 61 V variable types C0 51 C1 51 C3 52 ...
Page 159: ...144 Revision History ...
Page 161: ...E5ZN DeviceNet Communications Unit Cat No H119 E1 01 OPERATION MANUAL ...