20
Logic Functions
Section 1-5
Data That Can Be Set for Additional Outputs
Note
Turns OFF (0) when one of the errors shown in
occurs.
IMPORTANT
When additional output data is set, safety output terminals will reflect the out-
put status even in Idle Mode.
Note
(1) An additional output can be used only when the output terminals are set
as a single channel.
(2) An ON delay or OFF delay can be set for safety output terminals even
when an additional output is set.
Additional output data
Description
S
Same value as safety output
terminal
Outputs the same value as any safety output terminal.
S
Inverse value of safety output
terminal
Outputs the inverse value of any safety output terminal.
Reset required indication
Outputs a 1-Hz pulsing signal to trigger a reset input. The sig-
nal is output when resetting is enabled for one or more termi-
nals from among all the safety input terminals.
RUN Status Flag
Outputs the operating mode.
0: Not RUN mode
1: RUN mode
Normal Status Flag
Outputs the status.
0: Error (See note.)
1: Normal
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...