52
Node Address
Section 2-5
2-5
Node Address
Set the node address using the two rotary switches on the front panel of the
DST1-series Safety I/O Terminals. The default setting is 63. Set the tens digit
of the node address (decimal) using the left rotary switch and set the ones
digit using the right rotary switch. A value between 00 and 63 can be set.
If a node address between 64 and 99 is set, the node address can be set from
the Network Configurator.
IMPORTANT
• The node address must be set while the communications power supply is
turned OFF.
• Do not change the rotary switches while the power is ON. The DST1-
series Safety I/O Terminals will detect this as a change in the configura-
tion and will switch to fault state.
• Use a small flat-blade screwdriver to set the rotary switches, being careful
not to scratch them.
2-6
Configuration
Configure the DST1-series Safety I/O Terminals using the Network Configura-
tor. Refer to
for details on settings. Refer to the
Sys-
tem Configuration Manual
(Cat. No. Z905) for Network Configurator operating
procedures.
Ones digit of node address
Tens digit of node address
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...