139
DeviceNet Explicit Messages
Appendix 1
A-1-2
Explicit Messages
Reading General Status
Setting and Monitoring the Unit Conduction Time
Explicit
message
Read/
write
Function
Command
Response
Service
code
Class
ID
Instance
ID
Attribute
ID
Data size
General Sta-
tus Read
Read
Reads the speci-
fied slave’s status
flags (8 bits)
0E hex
95 hex
01 hex
65 hex
-
1 byte
Explicit
message
Read/
write
Function
Command
Response
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Unit Mainte-
nance Set
Value
Read
Reads the set
value for the Unit
Conduction Time
(unit: 0.1 h).
0E hex
95 hex
01 hex
73 hex
-
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Write
Writes the set
value for the Unit
Conduction Time
(unit: 0.1 h).
10 hex
95 hex
01 hex
73 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Unit Mainte-
nance
Present
Value
Read
Reads the present
value for the Unit
Conduction Time
(unit: 0.1 h).
0E hex
95 hex
01 hex
71 hex
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Unit Mainte-
nance Flag
Read
Reads the moni-
tor status of Unit
Conduction Time.
0E hex
95 hex
01 hex
72 hex
1 byte
00 hex: Within
range
01 hex: Over range
(over the monitor
value)
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...