144
DeviceNet Explicit Messages
Appendix 1
Setting and Monitoring the Test Output Point
Explicit
message
Read
/write
Function
Command
Response
Service
Code
Class
ID
Instance
ID
Attribute
ID
Data size
Terminal Main-
tenance Infor-
mation Monitor
Mode Read
Read
Reads the monitor
mode for mainte-
nance information
of the output (1 to
4) specified by the
instance ID.
0E hex
09 hex 01 to 04
hex
65 hex
-
1 byte
00 hex: Total ON
time mode
01 hex: Contact
operation
counter mode
Write
Writes the monitor
mode for mainte-
nance information
of the output (1 to
4) specified by the
instance ID
10 hex
09 hex 01 to 04
hex
65 hex
1 byte
00 hex: Total
ON time mode
01 hex: Contact
operation
counter mode
-
Output Set
Value for Total
On Time or
Contact Opera-
tion
Read
Reads the set value
for the total ON
time (unit: s) or
number of contact
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
0E hex
09 hex 01 to 04
hex
68 hex
-
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Write
Writes the set value
for the total ON
time (unit: s) or
number of contact
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
10 hex
09 hex 01 to 04
hex
68 hex
4 bytes
0000 0000 to
FFFF FFFF
hex
(0 to
4,294,967,295)
-
Output Total
ON Time or
Contact Opera-
tion Counter
Read
Read
Reads the set value
for the total ON
time (unit: s) or
number of contact
operations (unit:
operations) of the
output (1 to 4)
specified by the
instance ID.
0E hex
09 hex 01 to 04
hex
66 hex
-
4 bytes
0000 0000 to
FFFF FFFF hex
(0 to
4,294,967,295)
Output Total
ON Time or
Contact Opera-
tion Counter
Reset
Reset Resets the total ON
time or number of
contact operations
for time output (1 to
4) specified by the
instance ID.
05 hex
09 hex 01 to 04
hex
66 hex
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...