11
Description of Safety Functions
Section 1-4
If an error is detected, safety input data and individual safety input status will
turn OFF.
Setting Dual Channel Mode and Discrepancy Time
The consistency between signals on two channels can be evaluated. Either of
the following settings can be selected. This function monitors the time during
which there is a discrepancy in the logic between the two channels set as dual
channels. If the length of the discrepancy exceeds the set discrepancy time (0
to 65,530 ms, in increments of 10 ms), the safety input data and the individual
safety input status will turn OFF for both inputs.
IMPORTANT
The dual channel function is used with 2 consecutive inputs that start from
even input numbers: inputs 0 and 1, inputs 2 and 3, inputs 4 and 5, etc.
T0
External device
24 V
0 V
ON
OFF
IN0
Safety input 0
ON
OFF
ON
OFF
Status of safety
input 0
ON
* Normal
OFF
T0
External device
24 V
0 V
ON
OFF
IN0
Safety input 0
ON
OFF
ON
OFF
Status of safety
input 0
ON
* Error
OFF
Error
Remote
I/O data
Remote
I/O data
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...