130
Examples of Wiring for Each Application
Section 8-2
8-2-6
Safety Light Curtain Input
An example of the wiring and configuration when using the DST1-ID12SL-1 is
shown below.
Wiring
Configuration
V
G
IN0
T0
IN1
T1
E1
T2
G
GND
0V
+24V
F3SN-A
Emitter
Receiver
OSSD1
OSSD2
0V
+24V
E1: 24-V DC Power Supply (S8
@@
)
F3SN-A: Safety Light Curtain
Parameter
group
Parameter name
Value
Safety Input 0
0008
Safety Input 0 Channel Mode
Used as safety input
0009
Safety Input 0 Test Source
Not Used
0054
Dual Channel Safety Input 0/1 Mode
Dual Channel Equivalent
0055
Dual Channel Safety Input 0/1 Discrepancy Time
100 x 10 ms
Safety Input 1
0012
Safety Input 1 Channel Mode
Used as safety input
0013
Safety Input 1 Test Source
Not Used
Test Output 2
0003
Test Output 2 Mode
Power Supply Output