99
DST1-MD16SL-1
Section 5-2
The following table shows the terminal arrangement of the terminal blocks on
the DST1-MD16SL-1.
IMPORTANT
Power supply terminal V1 for the outputs is internally monitored. Supply the
voltage in the specified range (20.4 to 26.4 VDC). If the voltage is supplied
outside this range, voltage will not be supplied to the output circuits.
Terminals
Names
Functions
1,2
V0
Power terminals for the input devices and test outputs. (24 VDC)
11,12
G0
3 to 10
IN0 to IN7
Terminals for safety inputs
13 to 20
T0 to T3
Terminals for test outputs
21, 22
V1
Power terminals for the output devices. (24 VDC)
31, 32
G1
23 to 30
OUT0 to OUT7
Terminals for safety outputs
33 to 40
G1
Common terminals. Terminals 31 to 40 are internally connected.
I/O Power Supply
Circuit
Internal
Circuit
Test Output Circuit
Safety Input Circuit
V0
V0+
G0
T0...T3
IN0...IN7
I/O Power Supply
Circuit
Safety Output Circuit
V1
V1+
G1
OUT0
...OUT7
G1
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...