54
Editing Parameters
Section 3-1
3-1
Editing Parameters
Device parameters can be edited using any of the following methods.
1.
Double-click a device icon.
2.
Select a device, and then select
Device - Parameter - Edit
from the menu
bar.
3.
Select a device, and then click the
Edit Parameter
Button on the toolbar.
4.
Right-click the device and select
Parameter
- Edit
.
5.
Select the device, and then select
Device - Parameter - Wizard
.
Note
With Network Configurator version 2.0
@
or higher, basic parameters can be
set using a wizard. Using this parameter will reduce errors in the parameter
settings.
3-1-1
Setting Parameters Using the Wizard
With Network Configurator Ver. 2.0
@
or higher, I/O parameters for DST1-
series Safety I/O Terminals can be set using a wizard. This section explains
the procedure.
1.
Select a DST1-series Safety I/O Terminal, and then select
Device - Pa-
rameter - Wizard
. The following window will be displayed.
If there are no output terminals (DST1-ID12SL-1), the window for setting
input terminals will be displayed.
2.
In the window above, specify the type of device to be connected to each
terminal. The following types can be specified.
Type
Description
2 Safety Relays with welding check
(See note.)
Specify to connect to two Safety Relay
outputs (with welding check for each).
2 Safety Relays w/o welding check
(See note.)
Specify to connect to two Safety Relay
outputs (with no welding check).
1 Safety Relay with welding check
Specify to connect to one Safety Relay
output (with welding check).
1 Safety Relay w/o welding check
Specify to connect to one Safety Relay
output (with no welding check).
Other 2 Safety Outputs (See note.)
Specify to connect to two outputs without
welding check.
Other Safety Output
Specify to connect to one output without
welding check.
Door SW Lock
Specify to connect to an electromagnetic
door switch.
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...