124
Wiring and Configuration
Section 8-1
8-1
Wiring and Configuration
The following table shows input device connection methods and configuration.
Connected
device
Schematic diagram
Configuration
Reset switch
Connect the switch between IN0 and T0.
Safety Input used as “Single Channel input” with-
out test output.
Test output used as power supply output.
Connect the switch between 24 V DC and IN0.
Safety Input used as “Single Channel input” with-
out test output.
Emergency
stop switch
Door monitor
Connect the switches between IN0 and T0, and
IN1 and T1.
Safety Inputs used as “Dual Channel input” with
test output.
Test outputs used as “Pulse Test Output”.
Connect the switches between T0 and IN0, IN1.
Safety Inputs used as “Dual Channel input” with
test output.
Test output used as “Pulse Test Output”.
Connect the switches between 24 V DC and IN0,
IN1.
Safety Inputs used as “Dual Channel input” with-
out test output.
Safety
Light Curtain
Connect OSSD1 and OSSD2 to IN0 and IN1,
respectively.
Safety Inputs used as “Dual Channel input” with-
out test output.
IN0
T0
IN1
T1
IN0
T0
IN1
T1
24 V
IN0
T0
IN1
T1
IN0
T0
IN1
T1
IN0
T0
IN1
T1
24 V
OSSD2
OSSD1
OSSD2
OSSD1
IN0
T0
IN1
T1
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...