121
Maintenance
Section 7-4
Inspection Procedure
Check the items in the following table and correct any condition that is below
standard.
IMPORTANT
•
The maintenance interval for the relay contacts must not exceed a period
of 6 month to meet safety category 4 in accordance with EN 954-1.
• The G7SA-2A2B must be used when replacing safety relays.
7-4-3
Replacing the DST1
The network consists of the DeviceNet Unit (master) and DST1 Terminals.
The entire network is affected when a DST1 is faulty, so a faulty DST1 must
be repaired or replaced quickly. We recommend having spare DST1 Termi-
nals available to restore network operation as quickly as possible.
Precautions for Replacing the DST1
Observe the following precautions when replacing a faulty DST1.
After replacement, make sure that there are no errors in the new DST1.
When a DST1 is being returned for repair, attach a detailed description of the
problem and return the DST1 to your OMRON representative.
If there is a faulty contact, try wiping the contact with a clean, lint-free cloth
dampened with alcohol.
Settings after Replacing a DST1
After replacing a DST1, set the new DST1’s switches and configuration data
to the same settings that were used on the old DST1.
Inspection item
Details
Standard
Equipment
Environmental con-
ditions
Are ambient and panel tempera-
tures correct?
Refer to the specifications for
each DST1.
Thermometer
Are ambient and panel humidity
correct?
Refer to the specifications for
each DST1.
Hygrometer
Has dust or dirt accumulated?
No dust or dirt
Visual inspection
Installation condi-
tions
Is the DST1 installed securely?
No looseness
Phillips screwdriver
Are the connectors of the commu-
nications cables fully inserted?
No looseness
A flat-blade screwdriver
Are the external wiring screws
tight?
No looseness
A flat-blade screwdriver
Are the connecting cables undam-
aged?
No external damage
Visual inspection
Safety relay opera-
tion
Does the safety relay contact go to
OFF state?
No welded contacts
Visual inspection
!
WARNING
Safety functions may be impaired and serious injury may occasionally occur.
When replacing a device, configure the replacement device suitably and con-
firm that it operate correctly.
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...