xxi
Operating Environment Precautions
4
4
Operating Environment Precautions
■
Handle with Care
Do not drop the DST1 to the ground or excessive vibration or mechanical
shocks. The DST1 may be damaged and may not function properly.
■
Installation and Storage Environment
Do not use or store the DST1 in any of the following locations.
• Locations subject to direct sunlight
• Locations subject to temperatures or humidity outside the range specified
in the specifications
• Locations subject to condensation as the result of severe changes in tem-
perature
• Locations subject to corrosive or flammable gases
• Locations subject to dust (especially iron dust) or salts
• Locations subject to water, oil, or chemicals
• Locations subject to shock or vibration
Take appropriate and sufficient countermeasures when installing systems in
the following locations. Inappropriate and insufficient measures may result in
malfunction.
• Locations subject to static electricity or other forms of noise
• Locations subject to strong electromagnetic fields
• Locations subject to possible exposure to radioactivity
• Locations close to power supplies
This is a class A product. In residential areas it may cause radio interference,
in which case the user may be required to take adequate measures to reduce
interference.
■
Installation/Mounting
• Use the DST1 within an enclosure with IP54 protection or higher of IEC/
EN 60529.
• Use DIN rail (TH35-7.5 according to IEC60715) for placing the DST1 into
the control board.
• Mount the DST1 to DIN rails with attachments (TYPE PFP-M, not incor-
porated to this product), not to drop out of rails by vibration etc.
• Spacing should be available around the DST1 at least 50 mm from its top
and bottom surfaces for ventilation and wiring.
Control device
Requirements
Emergency stop switches
Use approved switches with a direct opening mechanism complying with
IEC/EN 60947-5-1.
Door interlocking switches
Limit switches
Use approved switches with a direct opening mechanism complying with
IEC/EN 60947-5-1 and capable of switching micro-loads of 4 mA at 24 V DC.
Safety sensors
Use approved sensors complying with the relevant product standards, regu-
lations, and rules in the country where it is used.
Relays with forcibly guided
contacts
Contactors
Use approved relays with forcibly guided contacts complying with EN 50205.
For feedback purpose, use devices with contacts capable of switching micro-
loads of 4 mA at 24 V DC.
Other devices
Evaluate whether devices used are appropriate to satisfy the requirements of
safety category.
Summary of Contents for DST1-ID12SL-1
Page 1: ...OPERATION MANUAL Cat No Z904 E1 06 DeviceNet Safety DST1 series Safety I O Terminals...
Page 2: ......
Page 3: ...DST1 series Safety I O Terminals Operation Manual Revised June 2011...
Page 4: ...iv...
Page 10: ...x...
Page 14: ...xiv...
Page 110: ...86 Remote I O Allocations Section 3 2...
Page 116: ...92 Indicators Section 4 2...
Page 134: ...110 DST1 XD0808SL 1 Section 5 4...
Page 146: ...122 Maintenance Section 7 4...
Page 159: ...135 Logic Terminal Wiring Examples Section 8 3...
Page 160: ...136 Logic Terminal Wiring Examples Section 8 3...
Page 178: ...154 Index...
Page 181: ...157 Revision History...