Appendix C
Error History Information
The following table shows the error information, detailed information, and content messages that are displayed in
the Master Error History window when the “Display Master Error History” command is executed.
Error
Detailed Information
Error
“Content” message
Code on
Info.
1
st
2 digits
2
nd
2 digits
Master’s
LEDs
0002
Code on
Node
PC interface error
PLC I/F Error.
F6
0006
Master’s
LEDs
address
where error
Initialization error with PC
Error occurred in Initial process for
PLC.
F5
000B
occurred
Routing table error
Data in Routing Table incorrect.
E5
0101
The other
node’s
node
Frame
identifier
Transmission
response
message
Not in network
Response message to be sent
discarded because self node not part
of network.
---
0103
address
(See note.)
faulty
Local node not
in network
Response message to be sent
discarded because of send error.
---
0109
Other node not
in network
Response message to be sent
discarded because partner node
busy.
---
0112
Incorrect
header
Response message to be sent
discarded due to wrong information
of message header.
---
0117
Source
node
address
Reception
response
message
Reception
buffer full
Received response message
discarded because self node’s
internal receiving buffer full.
---
0118
faulty
Incorrect
message
Received message incorrect and
then discarded.
---
0119
Target
node
address
Transmission
response
message
faulty
Other node
busy
Response message to be sent
discarded because self node busy.
---
0701
Code on
Node
Configuration data error
Configuration Data Error.
E8
0702
Master’s
address
I/O area overlap
Slave’s I/O Area duplicated.
d0
0703
LEDs
where error
occurred
I/O area range exceeded
Slave’s I/O Area out of valid
allocated range.
d1
0704
Slave not supported.
Unsupported Slave Station
connected.
d2
0705
Comparison error
(Slave doesn’t exist.)
Slave Station registered on Scan List
not exist.
d5
0706
Comparison error
(Slave I/O size mismatch)
Slave Station’s I/O Size not match
with registered information.
d5
0707
Communications error
Communication Error occurred in
Remote I/O communication.
d9
0708
Scan list operation couldn’t be
performed.
Scan List can not be operated.
C0 to C5
0709
PC mounting error
PLC Connecting Error.
E4
0781
Node address duplication
Node Address duplicated with
another node.
F0
0782
Bus Off error detected
Bus Off occurred.
F1
0783
Communications power supply
error
Power not fed for communication.
E0
0784
Transmission timeout
Send Time-Out occurred.
E2