5-10
AFP-400 Installation
PN 50253:A2 03/12/96
Combination Fire/Burglary Applications, continued
S2
J 6
Receiving Unit
Installing a Security
Tamper Switch into
the CAB-3
MPS-400 J5
Tamper
MPS-400
CAB-3 Series
Cabinet
Mounting location
(side opposite to
door hinges)
Installing the STS-1 Security Tamper Switch
For applications requiring transmission of burglary alarm information to a
central receiving unit, the control panel may be connected to an AM-2020 or
AFP-1010 provided with a NIB-96 network interface board. (For wiring
information, refer to Appendix B.) Configure the AM-2020/AFP-1010 for
Combination Fire/Security applications as outlined in the installation section
of the AM-2020/AFP-1010 manual. Burglar alarm zones are reported to the
AM-2020 through the NIB-96. Program AM-2020 networked monitor points
as a SARM type code (security alarm).
The control panel can communicate with any number of BURGLAR ALA type
code devices. To do so, program the points as follows:
1) Select the address of the monitor module(s) to be used for security; and
2) Set the type code to BURGLAR ALA.
Programming
Refer to the AFP-400
Programming Manual for
detailed instructions.
Circuit Wiring
Wire security monitoring devices as shown the Wiring Diagram for Propri-
etary Burglar Alarm Applications on the next page.
STS-1 Tamper
Switch
1) Install the STS-1 tamper switch onto the side of the CAB-3 series on side of
backbox opposite the door hinge.
2) Push the STS-1 switch through the opening in the backbox until the switch
snaps into place.
3) Install the magnet on the same side on the cabinet door as the lock. Push
the magnet through the opening in the door until the magnet snaps into
place.
4) Connect the STS-1 switch connector to J5 (Tamper) on the MPS-400.