AFP-400 Installation
PN
50253
:
A2 03/12/96
2-43
3) Set the DIP switches SP1 and SP2 according to the tables below.
1) Connect the printer with overall foil/braided-shield twisted paired cable
suitable for EIA-232 applications. Typically 50 feet maximum between
printer and control panel.
2) The printer communicates using the following protocol:
Remote Printers and CRTs
Connecting a Keltron
Printer
Connect a Keltron printer to the CPU-400 as follows:
1) Connect the printer cable to terminal TB1 on the CPU-400.
2) Connect the DB-25 connector to the EIA-232 port of the
Keltron printer.
3) Connect DC power from terminal TB2 on the MPS-400.
Keltron Printer
Model VS4095/5
DB-25
connector
CPU-400
Outputs are power limited
but are not supervised.
Setting up the Printer
Keltron remote printer
DC connections to MPS-400
(14 AWG)
MPS-400
TB2
Keltron Printer Connections
DIP Switch SP1
On
Off
SP1-1
X
SP1-2
X
SP1-3
X
SP1-4
X
SP1-5
X
SP1-6
X
SP1-7
X
SP1-8
X
DIP Switch SP2
On
Off
SP2-1
X
SP2-2
X
SP2-3
X
SP2-4
X
SP2-5
X
SP2-6
X
SP2-7
X
SP2-8
X
+
24 VDC
Set the...
To...
Baud rate
2400
Parity
Even
Data Bits
7