AFP-400 Installation
PN
50253
:
A2 03/12/96
2-59
The CMX module can control 2 amps of resistive load (on electronic devices)
or 1 amp of inductive load (on mechanical bells and horns). If more than one
CMX Notification Appliance Circuit is provided, install the power supervision
relay after the last CMX. Refer to Device Compatibility Document 15378 for
compatible notification appliances and relays.
SLC Wiring with CMX Control Modules
Style Y Circuits
CMX
Loop out
CPU-400
MPS-400
Do not loop wiring under
any terminals. Break wire
run to maintain supervi-
sion.
Typical NFPA Style Y Notification Appliance Circuit
Typical Style Y Wiring
Diagram
Listed Power
Supervision Relay
24 VDC Notification
Appliance
End-of-Line Resistor
47K, 1/2-watt
part number SSD A2143-00
(N-ELR in Canada)
The wiring diagram below shows an NFPA Style Y Notification Appliance Circuit
(all circuits are supervised and power-limited) using a CMX module. The
following table contains SLC wiring connections to the MPS-400 and CPU-400
as shown in the wiring diagram.
Module
Connect...
MPS-400
24V (+) to TB2-1
24V () to TB2-2
CPU-400
SLC (+) to TB5-1
SLC () to TB5-3
MPS-400 and CPU-400 SLC Connections
to next device
on loop
+