A-2
AFP-400 Installation
PN 50253:A2 03/12/96
ACS Annunciator Selection Group 1
ACS Point
Point
Red LED
Yellow LED
Switch
Comments
Number
Type
Indicates
Indicates
Function
1
Input
System Alarm
System Trouble
Acknowledge
2
Output
Not Used
Signal Silenced
Signal Silence
3
Output
Not Used
Program Mode
System Reset
4
Output
Not Used
Supervisory
Drill
5
Output
NAC #1 Active
NAC Trouble
Control NAC #1
6
Input
Not Used
PA/Maint Alert
Not Used
7
Input
Not Used
Low Battery
Not Used
8
Input
Not Used
AC Fail
Not Used
9
Input
Zone 1 Active
Zone 1 Trouble
Not Used
10
Input
Zone 2 Active
Zone 2 Trouble
Not Used
11
Input
Zone 3 Active
Zone 3 Trouble
Not Used
12
Input
Zone 4 Active
Zone 4 Trouble
Not Used
13
Input
Zone 5 Active
Zone 5 Trouble
Not Used
14
Input
Zone 6 Active
Zone 6 Trouble
Not Used
15
Input
Zone 7 Active
Zone 7 Trouble
Not Used
16
Input
Zone 8 Active
Zone 8 Trouble
Not Used
17
Input
Zone 9 Active
Zone 9 Trouble
Not Used
18
Input
Zone 10 Active
Zone 10 Trouble
Not Used
19
Input
Zone 11 Active
Zone 11 Trouble
Not Used
20
Input
Zone 12 Active
Zone 12 Trouble
Not Used
21
Input
Zone 13 Active
Zone 13 Trouble
Not Used
22
Input
Zone 14 Active
Zone 14 Trouble
Not Used
23
Input
Zone 15 Active
Zone 15 Trouble
Not Used
24
Input
Zone 16 Active
Zone 16 Trouble
Not Used
25
Input
Zone 17 Active
Zone 17 Trouble
Not Used
26
Input
Zone 18 Active
Zone 18 Trouble
Not Used
27
Input
Zone 19 Active
Zone 19 Trouble
Not Used
28
Input
Zone 20 Active
Zone 20 Trouble
Not Used
29
Input
Zone 21 Active
Zone 21 Trouble
Not Used
30
Input
Zone 22 Active
Zone 22 Trouble
Not Used
31
Input
Zone 23 Active
Zone 23 Trouble
Not Used
32
Input
Zone 24 Active
Zone 24 Trouble
Not Used
33
Input
Zone 25 Active
Zone 25 Trouble
Not Used
34
Input
Zone 26 Active
Zone 26 Trouble
Not Used
35
Input
Zone 27 Active
Zone 27 Trouble
Not Used
36
Input
Zone 28 Active
Zone 28 Trouble
Not Used
37
Input
Zone 29 Active
Zone 29 Trouble
Not Used
38
Input
Zone 30 Active
Zone 30 Trouble
Not Used
39
Input
Zone 31 Active
Zone 31 Trouble
Not Used
40
Input
Zone 32 Active
Zone 32 Trouble
Not Used
41
Input
Zone 33 Active
Zone 33 Trouble
Not Used
42
Input
Zone 34 Active
Zone 34 Trouble
Not Used
43
Input
Zone 35 Active
Zone 35 Trouble
Not Used
44
Input
Zone 36 Active
Zone 36 Trouble
Not Used
45
Input
Zone 37 Active
Zone 37 Trouble
Not Used
46
Input
Zone 38 Active
Zone 38 Trouble
Not Used
47
Input
Zone 39 Active
Zone 39 Trouble
Not Used
48
Input
Zone 40 Active
Zone 40 Trouble
Not Used
49
Input
Zone 41 Active
Zone 41 Trouble
Not Used
50
Input
Zone 42 Active
Zone 42 Trouble
Not Used
51
Input
Zone 43 Active
Zone 43 Trouble
Not Used
52
Input
Zone 44 Active
Zone 44 Trouble
Not Used
53
Input
Zone 45 Active
Zone 45 Trouble
Not Used
54
Input
Zone 46 Active
Zone 46 Trouble
Not Used
55
Input
Zone 47 Active
Zone 47 Trouble
Not Used
56
Input
Zone 48 Active
Zone 48 Trouble
Not Used
57
Input
Zone 49 Active
Zone 49 Trouble
Not Used
58
Input
Zone 50 Active
Zone 50 Trouble
Not Used
59
Input
Zone 51 Active
Zone 51 Trouble
Not Used
60
Input
Zone 52 Active
Zone 52 Trouble
Not Used
61
Input
Zone 53 Active
Zone 53 Trouble
Not Used
62
Input
Zone 54 Active
Zone 54 Trouble
Not Used
63
Input
Zone 55 Active
Zone 55 Trouble
Not Used
64
Input
Zone 56 Active
Zone 56 Trouble
Not Used
Table A-1 ACS Annunciator Selection Group 1