AFP-400 Installation
PN 50253:A2 03/12/96
1-13
Indicating Circuit and Control Modules
The AFP-400 supports the following modules:
Indicating Circuit Module (ICM-4)
Indicating Circuit Expander (ICE-4)
Control Relay Module (CRM-4)
Control Relay Expander (CRE-4)
Auxiliary Relay Module (ARM-4)
Ribbon Connector
For
connecting the ARM-4 to
the driving relay module.
Slide-in Labels
Provided with ICM-4
and CRM-4 modules.
Auxiliary Bell Power
Harness.
Provided with ICM
and CRM modules.
Indicating Circuit and Control Relay Modules
Overview
Module
Function
Circuit Rating
ICM-4
Provides four Notification
Appliance Circuits for Style Y or
Style Z operation. Circuits are
field-programmable to respond to
a single initiating zone, a group of
zones, or all initiating zones.
Maximum signaling current
is 3 amps of total current,
limited by the power
supply.
ICE-4
Expands the ICM-4 to a total of
eight Notification Appliance
Circuits (Style Y or Style Z).
Identical to the ICM-4.
CRM-4
Provides four standard dry Form-C
relay contacts. Each relay is
field-programmable to respond to
a single initiating device circuit, a
group of circuits, or all initiating
device circuits. Each relay features
manual On/Off control switches
and can be disabled or enabled.
Contacts rated for 5 amps
at 120 VAC or 28 VDC
(resistive).
CRE-4
Expands the capacity of the
Control Relay Module (CRM-4) to
eight Form-C alarm relays.
Identical to the CRM-4.
ARM-4
Provides four auxiliary Form-C
relays that can be controlled by a
CRM-4 or CRE-4 relay module.
Normally-open contacts
rated for 20 amps and the
normally-closed contacts
are rated for 10 amps at
125 VAC and 30 VDC
(resistive).
Modules
Harnesses and Labels
Indicating Circuit and Control Relay Modules come with the following: