AFP-400 Installation
PN 50253:A2 03/12/96
5-5
Network Interface Board
The Network Interface Board (NIB-96) is a microprocessor-controlled module
that connects slave fire alarm control panels to a master fire control panel.
Usually, NIB-96 modules are physically located in each slave control panel,
which can contain 8-96 input/output points. This section contains board and
wiring information for connecting an NIB-96 to an AFP-400 control panel.
Overview
SIZE Select switch
SLC Start Address
switch
SLC and EIA-485
Connections
SLC On-Line LED
EIA-485 On-Line LED
Trouble LED
Power In
Network Interface Board Components
Item
Description
Trouble LED
Yellow LED lights during loss of communications on EIA-485 or
SLC loop.
EIA-485 On Line LED Green LED blinks during communication with the slave FACP.
SLC On line LED
Green LED blinks during communication with the master FACP.
SLC and EIA-485
connections
All connections are power-limited and supervised. See Sections
3, 4 and 5 for details on connection requirements. See diagram
below for terminal assignment
Power In
Connects NIB to the Main Power Supply (if not mounted in an
ICA-4/L).
Power Out
Connection to other equipment.
Power connector
Power connection for the AM2020/AFP1010 slave.
SLC Start Address
switch
Set to 01 through 99. (Note that the sum of ADDRESS and SIZE
cannot exceed 99.)
SIZE Select switch
Switch that lets you select the number of points (select 1-8)
monitored on the slave panel.
Continued on the next page...
Network Interface Board
NIB-96 Components
Power connector
Circuit
Requirements
Power
24 VDC power limited
Standby
22 mA
Alarm
22 mA
NIB-96 Power Requirements
NIB-96 Assembly
Power Out