2-44
AFP-400 Installation
PN
50253
:
A2 03/12/96
Remote Printers and CRTs
Connecting a CRT
Connect a CRT to the CPU-400 as follows:
1) Connect one end of the cable to terminal TB2 on the CPU-400.
Connect
To CPU terminal...
TX (pin 3)
TB2-1
RX (pin 2)
TB2-2
REF (pin 7)
TB2-3
2) Plug the DB-25 connector to the EIA-232 port of the CRT.
Connecting Multiple Printers, CRTs, or Combination requires changing the
CRT-2 setup using the F1 (Quick) menu:
Set Host/Printer=EIA/AUX.
Set EIA Data Format=8/1/N.
If the Aux device is a printer, set Printer and AUX Data Format=7/1/E.
If the AUX device is a second CRT, set AUX Data Format=8/1/N.
Connect multiple devices as shown in the following diagram.
to CPU-400 TB4-2
to CPU-400 TB4-1
to CPU-400 TB4-3
3
2
7
To EIA Port of next CRT or PRN
To AUX Port of CRT
To EIA Port of CRT
with keyboard
For complete information on
setting up the CRT-2, refer to
Appendix E, Terminal
Interface Protocol.
Connecting Multiple
Printers, CRTs, or CRT/PRN
Combination
For terminal interface and
protocol information, refer
to Appendix E.
DB-25 connector
CRT
Connecting a CRT
twisted
pair
CPU-400
Connecting Multiple Printers, CRTs, or CRT/PRN Combinations