AFP-400 Installation
PN 50253:A2 03/12/96
E-3
Using the CRT-2 for Read Status
Overview
This section shows how to do Read Status functions from a CRT-2.
Rd Point=1, Rd Alm/Tbl=2, All Points=3, Hist:Step=4/All=5, Ala-Hist:Step=6/
Al=7
F1
From the Read Status menu, you can select options 1-5.
Continued on the next page...
Access the Read Status function from the CRT-2 by following these steps.
1) Turn on the CRT-2, which is connected to the control panel.
2) Press the Read Status function key F1. The control panel displays the
Read Status menu options:
Accessing Read Status
Options
Function
Lets you...
Read Point
Read the status of any point in the system (detectors,
modules, panel circuits, software zones, and system
parameters).
Alm/Tbl Status
Display a list of all devices in the system that are in
alarm or trouble.
Read All Points
Display a list of all points programmed in the system.
This list will display the staus of all addressable
detectors, modules, panel circuits, system parameters
and software zones.
History Step
Step through the history buffer one event at a time.
History-All
Send the entire history buffer to the CRT, from the
most recent event to the oldest event.
Table E-4 Read Status Functions