AFP-400 Installation
PN
50253
:
A2 03/12/96
2-33
Notification Appliance Circuits Current Configuration
These four NACs share
3 amps of one
AVPS-24 (#1).
These eight NACs
share the total
3 amps of the
second AVPS-24
(#2).
For this configuration (using two AVPS-24 supplies to power an ICM-4 or ICE-4),
cut jumper JP1 located above J5 and J6.
These four NACs share
3 amps of one AVPS-24
(#2).
These four NACs share
3 amps of one AVPS-24
(#1).
ICM-4 or ICE-4
These two circuits
share 3 amps of
one AVPS-24 (#2).
These two circuits
share 3 amps of one
AVPS-24 (#1).
AVPS-24 #1
AVPS-24 #2
AVPS-24 #2
AVPS-24 #1
AVPS-24 #2
J5
J6
J5
J6
J5
J5
J5
J6
ICM-4
ICM-4
ICE-4
ICM-4
ICE-4
ICM-4
AVPS-24 #2
AVPS-24 #1
Typical Supply/
Notification Circuit
Configurations