2-32
AFP-400 Installation
PN
50253
:
A2 03/12/96
Notification Appliance Circuit Current Configuration
The total current available from any group of Notification Appliance Circuits
cannot exceed the following:
3.0 A when powered from the AVPS-24; or
1.25 A when powered from an MPS-400 output.
The following figure shows the bottom wire connections of the ICM-4 and
the ICE-4 modules.
Total in these figures
assumes that no notification
appliance power is drawn
for any other purpose.
Overview
The following figures show typical power supply to Notification Appliance
Circuit configurations.
Typical Supply/
Notification Circuit
Configurations
ICM-4
J5
J6
J5
ICE-4
MPS-400
J5
J6
ICM-4
MPS-400
TB2-1 and TB2-2
1.25 A
TB2-3 and TB2-4
1.25 A
MPS-400
J5
ICM-4
J5
ICM-4
TB2-1 and TB2-2
1.25 A
TB2-3 and TB2-4 1.25 A
TB2-1 and TB2-2
1.25 A
These two NAC circuits share 1.25 A
from MPS-400 TB2-3 and TB2-4.
These eight NAC Circuits
share 1.25 A.
These two NAC circuits share 1.25 A
from MPS-400 TB2-1 and TB2-2.
These NAC circuits share 1.25 A
from MPS-400 TB2-1 and TB2-2.
These NAC circuits share 1.25 A
from MPS-400 TB2-3 and TB2-4.
Continued on the next page...
connector
orientation
MPS Bell Power
Harness (71093)
black wire
blue wire