NN10078-911 SN06.2 Preliminary 02.03 March 2004
97
Copyright © 2004, Nortel Networks
Nortel Networks Confidential
7
Using the right and left edges of the FMU faceplate, remove the
appropriate card from the PCIU.
8
Align the new card with the card guides.
9
Make a clean, direct insertion, and be sure to fully seat the card.
Note:
Do not rely on the thumb screw to seat the card.
10
TIghten the thumb screw.
11
Re-insert the two fan units removed by holding onto the
faceplate of the fan in one hand and folding the fan assembly flat
(align with the bar on the fan unit), then inserting it into the slot
of the cooling unit. Once fan starts sliding into the slot of the
cooling unit, release the fan and allow it to return to its upright
position.
12
Pushing on the faceplate of the fan units, carefully re-seat them
into the NTLX55 cooling units in shelf positions XX and YY.
13
Ensure that the green LEDs on the faceplate of the fan units are
lit and the fan are running.
14
Move the lock latches on the fan units to the locked position as
indicated on the faceplate of the fans.
15
Lower the cover of the PCIU shelf and move the latches to the
locked position, as indicated on the cover.
16
You have completed this procedure.