NN10078-911 SN06.2 Preliminary 02.03 March 2004
89
Copyright © 2004, Nortel Networks
Nortel Networks Confidential
26
Ensure that the replacement card has the same PEC and
release number.
Note:
Refer to the
Data Schema Reference Manual or the
data schema section of the
Translation Guide, as appropriate,
for information about Table MNCKTPAK.
27
Insert the replacement CEM card into the shelf.
28
Open the locking levers on the card.
29
As shown in the following figure, hold the card by the face plate
with one hand while supporting the bottom edge with the other
hand. Gently slide the card into the shelf.
DANGER
Equipment malfunction
Use a replacement card with the same PEC
and release to avoid equipment malfunction. If
the replacement card has a different PEC or
release, change the datafill in Table
MNCKTPAK to match the replacement card
before inserting it in the slot.