Instruction manual
OCM Pro CF
page 150
OCM Pro CF - Rev. 09 as of 07.06.2016
®
Fig. 9-156 Selecting the analog output simulation
Channel number
Choose the analog output which is to be simulated by entering the respective
number from 1 – 4 or by using the >left< or >right< arrow keys in the simulation
main menu.
Simulation
Enter the desired value in mA here and confirm with Enter in order to directly
output it on the according clamp assigned to the analog output selected
before.
Fig. 9-157 Executing the simulation
9.7.4 Cal-Menu "Relay Outputs “
Select the desired relays to be simulated by pressing the >left< or >right< arrow
keys. The relay number chosen is going to be indicated in the first line of the
output table.
The arrow keys >up< or >down< will either directly enable or disable the relay
selected previously.
After selecting >Relay Outputs< the PIN must be entered once again. This en-
sures to keep unauthorised persons away from executing simulations during op-
eration.
Fig. 9-158 Relay simulation