Control OPEN:
here you can enter the internal name (not required) as well as
the logic function of relay 5 (normally closed or normally open). Select by
pressing >ALT<.
Note
Relay 4 is defined as >slide valve CLOSED<, relay 5 as >slide valve OPEN<
by hardware configuration. This assignment cannot be modified!!
Note
If >normally open< has been selected, the relay is going to energise for the
calculated period of time if the according setpoint has been reached. If set to
>normally closed< the relay will energise immediately after the parameters
have been set and is going to de-energise for the calculated period of time as
soon as the respective setpoint has been equalled.
End switch
This menu allows to assign functions and their logic to the corresponding digital
inputs.
The channel number is equivalent to the number of the digital input.
Channel number 1 = digital input 1, channel number 2 = digital input 2 etc.
By selecting channel number and function subsequently it is possible to define
which end switch is connected to which signal input.
The name is for internal use only and does not have to be set.
Modifying the logic (inverse / non-inverse) allows you to monitor cable breaks of
end switch connections.
Fig. 9-80
End switch assignment
Fig. 9-81
Possible functions