1 Menu tree
1.8 MAIN MENUE – Doors
144
FST_HB.EN04/03
1.8 MAIN MENUE – Doors
All menu items with adjustable values can be deactivated by entering the
value “0”.
Menu item
Description
Setting
Doors Basic –
Number Doors
Number of car doors.
0 ... 3
Doors Basic –
Apply–ALL
The settings in
Doors – Selective
automatically apply
to all car doors.
YES
NO
Doors Basic –
Cam Delay
Delay between reaching the levelling position or the zone area
and dropping off of the lock-cam curve (locking solenoid for
unlocking the shaft doors, FSM X6.5).
0 ... 4 sec
Doors Basic –
Cam Time Max
Maximum activation time of the locking solenoid. Prevents the
solenoid from damage in case of failures. After this time has
elapsed output FSM X6.5 for the locking solenoid is switched
off, independent from the state of the controller.
0010 ... 9999 sec
Doors Basic –
Lock Delay
Maximum delay between closing of car door contact and shaft
door or locking contact when closing the doors. If this time is
exceeded the error
DOOR LOCK TIMEOUT
is displayed.
The car door opens for the set
Retry Time
and then closes
again.
0 ... 4 sec
Doors Basic –
Lock Fail Max
Maximum number of consecutive lock fails (
DOOR LOCK
TIMEOUT
). All landing and in-car calls will be deleted and the
error
DOOR LOCK RETRY CNT
is displayed.
0 ... 10
Doors Basic –
Lock Fail Open
Door allocation after lock fail:
“One”: Only the car door last opened opens after a lock fail
(
DOOR LOCK TIMEOUT
).
“All”: All car doors open after a lock fail (
DOOR LOCK
TIMEOUT
).
ONE
ALL
Doors Basic –
SCCT Debounce
Delay between closing of the safety circuit and activation of
the drive contactors when starting (prevents contactor
bouncing).
0 ... 2.5 sec
Doors Basic –
Retry Time
Opening time of the car door before closing again after a lock
fail (
DOOR LOCK TIMEOUT
).
0 ... 4 sec
Doors Basic –
Open Delay
Delay before opening the doors when the levelling position
has been reached (see “Door times diagram” on page 147).
0 ... 4 sec
Doors Basic –
Bypass t–OFF
Delay when switching off the safety circuit bypass relay K20 of
the VSM.
0 ... 2 sec
Doors Basic –
Bypass t–ON
Delay when switching on the safety circuit bypass relay K20 of
the VSM.
0.1 ... 2 sec
Doors Basic –
Pre-Opening
Enable approach with car and shaft doors open. This
parameter can only be activated when using the A6 Safety
Circuit! The following steps are required to deactivate an
integrated A6 Safety Circuit:
-
Set
Pre-Opening = NO
-
Set
Relevelling = NO
-
Disconnect power supply of the safety circuit (terminals 518,
519)
YES
NO
Summary of Contents for FST
Page 1: ...Manual Field Bus Controller ...
Page 6: ...Table of Contents 4 FST_HB EN04 03 ...
Page 43: ...4 Technical Data 4 2 FST Controller FST_HB EN04 03 41 Fig 4 2 FST Controller ...
Page 98: ...4 Technical Data 4 13 Trailing cable 96 FST_HB EN04 03 Fig 4 14 Trailing cable version 1 ...
Page 102: ...4 Technical Data 4 13 Trailing cable 100 FST_HB EN04 03 ...
Page 104: ...1 Menu tree 1 1 General 102 FST_HB EN04 03 Fig 1 1 FST Controller menu tree part 1 ...
Page 105: ...1 Menu tree 1 1 General FST_HB EN04 03 103 Fig 1 2 FST Controller menu tree part 2 ...
Page 106: ...1 Menu tree 1 1 General 104 FST_HB EN04 03 Fig 1 3 FST Controller menu tree part 3 ...
Page 107: ...1 Menu tree 1 1 General FST_HB EN04 03 105 Fig 1 4 FST Controller menu tree part 4 ...
Page 108: ...1 Menu tree 1 1 General 106 FST_HB EN04 03 Fig 1 5 FST Controller menu tree part 5 ...
Page 109: ...1 Menu tree 1 1 General FST_HB EN04 03 107 Fig 1 6 FST Controller menu tree part 6 ...
Page 110: ...1 Menu tree 1 1 General 108 FST_HB EN04 03 Fig 1 7 FST Controller menu tree part 7 ...
Page 111: ...1 Menu tree 1 1 General FST_HB EN04 03 109 Fig 1 8 FST Controller menu tree part 8 ...
Page 112: ...1 Menu tree 1 1 General 110 FST_HB EN04 03 Fig 1 9 FST Controller menu tree part 9 ...
Page 160: ...6 Error List 6 4 Error messages 158 FST_HB EN04 03 ...