5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
72
5293079/01 EN
VACUTAP
®
VM-Ex
2. Insert lifting gear in the brackets on the diverter switch insert carrier plate
and position vertically above the diverter switch insert.
Figure 56: Brackets on carrier plate
3. Lift out diverter switch insert slowly and vertically.
Figure 57: Lifting out diverter switch insert
4.
CAUTION!
An unstably positioned diverter switch insert may tip, re-
sulting in injuries and property damage. Place the diverter switch insert on
a level surface and secure it against tipping.
5. Note down whether the diverter switch insert is in the final end position on
side A or side B. The vacuum interrupter is closed on the side that is in
the final end position. In the example in the appendix, side B is in the final
end position.
Summary of Contents for VACUTAP VM-Ex
Page 1: ...On load tap changer VACUTAP VM Ex Installation and commissioning instructions 5293079 01 EN ...
Page 208: ......