5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
118
5293079/01 EN
VACUTAP
®
VM-Ex
2. Insert lifting gear in the brackets provided on the diverter switch insert car-
rier plate and position vertically above the diverter switch insert.
Figure 123: Brackets on carrier plate
3. Ensure that diverter switch insert is in the final end position on the same
side as when it was removed (side A or side B). The vacuum interrupter is
closed on the side that is in the final end position. In the example in the
appendix, side B is in the final end position, see appendix.
4. By turning the coupling tube, align it in such a manner that the red trian-
gles on the coupling tube and carrier plate match up.
Figure 124: Coupling tube