5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
147
5293079/01 EN
VACUTAP
®
VM-Ex
5. Take off the slotted head screw for potential tie-in and remove the termi-
nal box cover with wire.
Figure 171: Terminal box cover
6. Remove screw for the protective cover and take off the protective cover.
Figure 172: Terminal box cover and protective cover
7. Guide explosion-certified cable through cable bushing and into protective
relay. Ensure that the cable gland is well connected and sealed.
8. Connect electric cables with cable cross-section of 1…4 mm
2
to connec-
tion terminals in accordance with connection diagram.
9. Insert the protective cover and secure using the screw.