5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
46
5293079/01 EN
VACUTAP
®
VM-Ex
6. Carefully lower the oil compartment vertically and align the position of
both coupling parts and attachment points of the oil compartment and se-
lector with one another. The correct position of the two coupling parts is
shown in the adjustment plans supplied.
7. Screw selector bracket onto oil compartment.
Figure 24: Oil compartment and selector screwed down
8.
Screw tap-selector connecting leads to connecting piece with care.
Comply with specified tightening torque and secure screw connection.
Failure to do so may result in damage to the on-load tap-changer and
transformer.
Figure 25: Screwing on the tap-selector connecting leads
1 Hexagon screw
4 Tap-selector connecting lead
2 Screening cap
5 Connecting piece
3 Washer