5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
131
5293079/01 EN
VACUTAP
®
VM-Ex
6. Align diverter switch insert such that the red triangles at the top of the en-
ergy accumulator and on the on-load tap-changer head are opposite one
another. Slowly lower diverter switch insert.
Figure 148: Aligning diverter switch insert
7. Ensure correct position of carrier plate in on-load tap-changer head. Area
marked red must remain free.
8. Secure carrier plate of diverter switch insert with screws for standard
transformer version or nuts for bell-type tank transformer version and
safety elements.
Figure 149: Carrier plate of diverter switch insert for standard transformer version
Figure 150: Carrier plate of diverter switch insert for bell-type tank transformer version