5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
89
5293079/01 EN
VACUTAP
®
VM-Ex
5.4.1.3 Inserting on-load tap-changer into supporting structure
1.
NOTICE!
Tensile forces can lead to damage and malfunctions on the on-
load tap-changer. Using spacers, insert the on-load tap-changer vertically
into the supporting structure (maximum 1° deviation from the vertical) so
that the on-load tap-changer reaches its final installation height and only
has to be raised a maximum of 5...20 mm once the tap winding and the
on-load tap-changer take-off lead have been connected and the bell-type
tank fitted.
Figure 82: On-load tap-changer with spacers on supporting structure
2. Temporarily fasten on-load tap-changer to supporting structure. The sup-
porting flange has through holes for this purpose.
Figure 83: Fastening the on-load tap-changer