5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
108
5293079/01 EN
VACUTAP
®
VM-Ex
2. Insert lifting gear in the brackets on the diverter switch insert carrier plate
and position vertically above the diverter switch insert.
Figure 107: Brackets on carrier plate
3. Lift out diverter switch insert slowly and vertically.
Figure 108: Lifting out diverter switch insert
4.
CAUTION!
An unstably positioned diverter switch insert may tip, re-
sulting in injuries and property damage. Place the diverter switch insert on
a level surface and secure it against tipping.
5. Note down whether the diverter switch insert is in the final end position on
side A or side B. If the diverter switch insert is in the final end position on
side A, the vacuum interrupter on side A is closed, and vice versa. In the
example in the appendix, the diverter switch insert is in the final end posi-
tion on side B.