5. Position the wire for the terminal box cover and affix using the slotted
head screw.
Figure 164: Terminal box cover
6. Attach the terminal box cover and secure with screws.
Figure 165: Terminal box cover
5.5.2.3 Installing protective relay in piping
Ensure the following for installation and proper function of the protective re-
lay:
1. Ensure that there are no foreign bodies in the piping or in the oil conserva-
tor.
2. Install protective relay such that it can be easily accessed for subsequent
maintenance work.
3. Install protective relay with good support and free from vibrations.
4. The test buttons must be at the top.
5. The interior diameter of the piping must be at least 25 mm.