5 Mounting
Maschinenfabrik Reinhausen GmbH 2020
53
5293079/01 EN
VACUTAP
®
VM-Ex
7. Screw the on-load tap-changer head to the mounting flange.
Figure 32: Screwing the on-load tap-changer head to the mounting flange
8. Reattach the connecting leads for an on-load tap-changer with potential
connection unit or an on-load tap-changer with 3W/2W/3G change-over
selector.
Figure 33: Fitting connecting leads
5.3.3 Connecting the tap winding and on-load tap-changer take-off
lead
NOTICE
Damage to the on-load tap-changer!
Connecting leads that place mechanical strain on the on-load tap-changer
will damage the on-load tap-changer.
► Establish connections carefully.
► Do not twist connection contacts.
► Connect connecting leads without warping or deforming.
► If necessary, use an expansion loop for connecting leads.
► Fit screening caps provided to screw connections.