App
- 157
Appendix 5 Method of replacing High Performance model QCPU with Universal model QCPU
APPENDICES
(2) Method of replacing High Performance model QCPU with Universal
model QCPU
(a) When the parameter-valid drive is set to the standard ROM in the High
Performance model QCPU
(Continued on next page)
TableApp.81 When the parameter-valid drive is set to the standard ROM
Setting in High Performance model QCPU
Setting in Universal model QCPU
Boot file setting of PLC parameter
No boot file setting
Change the setting so that the Universal model QCPU can refer to the
parameters in the standard ROM.
• Changes in parameter setting are not required.
• Delete parameters that exist in the program memory and memory card. *2
Contents of boot file setting
(No boot file setting for parameters)
Change the setting so that programs are stored in the program memory in the
first place, instead of booting from the standard ROM.
• Delete all settings for parameter on the Boot file setting tab of PLC
parameter.
• Delete parameters that exist in the program memory and memory card. *2
• Move the programs with boot setting into the program memory from the
standard ROM. *1
Contents of boot file setting
Change the setting so that programs and parameters are stored in the program
memory in the first place, instead of booting from the standard ROM.
• Move the programs and parameters with boot setting into the program
memory from the standard ROM. *1
• Delete all settings for parameter on the Boot file setting tab of PLC
parameter.
Contents of boot file setting
(No boot file setting for parameters)
Change the setting so that the Universal model QCPU can refer to the
parameters in the memory card and programs shall be booted from the
memory card to the program memory.
• Move the parameters in the standard ROM into the memory card.
• Make setting so that programs are booted from the memory card to the
program memory on the Boot file setting tab of PLC parameter. *3
Contents of boot file setting
Delete all settings for data other than program and parameter in the boot file
setting. Since these data can be used even not stored in the program memory,
it is not necessary to transfer them to the program memory. Or, change the
setting so that they are stored in the program memory in the first place.
• Delete all settings for data other than program and parameter on the Boot
file setting tab of PLC parameter.
• Move the data other than programs and parameters into the program
memory as needed.
Type
Transfer from
Transfer to
Program
Standard ROM Program memory
Type
Transfer from
Transfer to
Program
Standard ROM Program memory
Parameter
Standard ROM Program memory
Type
Transfer from
Transfer to
Program
Memory card
Program memory
Type
Transfer from
Transfer to
Program
Memory card
Program memory
Parameter
Memory card
Program memory