6.22 High Speed Interrupt Function
6.22.4 Restrictions
6
- 177
1
O
verv
iew
2
Per
fo
rma
nce
S
p
ecifica
tio
n
3
S
equ
en
ce P
ro
g
ra
m
Co
nfig
ura
tio
n a
nd
E
xecut
io
n Co
nd
iti
o
ns
4
I/O N
unb
er
Assig
n
m
e
nt
5
Me
mor
ie
s a
nd
File
s
Ha
nd
led
by CP
U Mo
du
le
6
Func
tions
7
Co
mmu
nic
a
tion
us
in
g
bu
ilt
-i
n E
th
e
rne
t po
rt
s o
f
CP
U mod
u
le
8
Co
mm
un
icatio
n
w
ith
Int
e
lli
ge
nt
Fun
ction
Mo
du
le
(3) Items that have priorities over the high speed interrupt when interrupt is
disabled
(4) Items other than (1) to (3)
(a) Interrupt program setting/fixed scan program setting in PLC parameter
dialog box
If "High speed execution" is selected at the "Interrupt program/fixed scan
execution program setting" section on the "PLC system" tab screen in the "(PLC)
parameter" dialog box of GX Developer, this setting is invalid for the high speed
interrupt function.
(b) High speed buffer transfer
Using the file registers outside the setting range (range in excess of the maximum
number of points) for high speed buffer transfer does not result in an error and
does not transfer data to outside the range. (The contents of the other devices are
not corrupted.)
(c) Precautions for program creation
As in the other interrupt programs, there are the following items as precautions for
program creation. (
Table6.50 Items that hold high speed interrupt by interrupt disable
No.
Item
Precaution
1
Instruction
Interrupt is disabled during instruction execution.
2
Link refresh
Interrupt is disabled during refresh (bus access).
For
CC-Link IE controller network,
MELSECNET/H, CC-Link or intelligent function module refresh, waiting time
is max. 37.5 s when modules are mounted on main base or max. 40 s when they are mounted on
extension base.
3
Multiple program
execution
When multiple programs are run, interrupt is disabled during program switching. Waiting time is 30 s.
When high speed interrupt function has been set, the recommended number of programs is 1.
4
Monitor
For ladder monitor, device batch-monitor or device entry monitor, waiting time is as follows.
(0.096 number of device 20) s
5
AC DOWN
Waiting time is max. 20ms for high speed interrupt start.