6.11 Monitor Function
6.11.1 Monitor condition setting
6
- 51
1
O
verv
iew
2
Per
fo
rma
nce
S
p
ecifica
tio
n
3
S
equ
en
ce P
ro
g
ra
m
Co
nfig
ura
tio
n a
nd
E
xecut
io
n Co
nd
iti
o
ns
4
I/O N
unb
er
Assig
n
m
e
nt
5
Me
mor
ie
s a
nd
File
s
Ha
nd
led
by CP
U Mo
du
le
6
Func
tions
7
Co
mmu
nic
a
tion
us
in
g
bu
ilt
-i
n E
th
e
rne
t po
rt
s o
f
CP
U mod
u
le
8
Co
mm
un
icatio
n
w
ith
Int
e
lli
ge
nt
Fun
ction
Mo
du
le
(2) Monitor Stop Condition Set Up
Choose [Online] [Monitor] [Monitor stop condition setup] to open the [Monitor
Stop Condition] dialog box. Figure 6.34 shows an example of stopping a monitoring
operation at the leading edge of Y71.
(a) When "Step No." is specified:
Monitoring is stopped when the status at execution of the specified step becomes
as specified.
The specification method for the execution status is shown below:
• When the operation of the specified step changes from the non-execution
status to the execution status : < P >
• When the operation of the specified step changes from the execution status
to the non-execution status : < F >
• Always only when the operation of the specified step is in execution : <ON>
• Always only when the operation of the specified step is in non-execution :
<OFF>
• Always regardless of the status of the operation of the specified step :
<Always>
When "Step No." is not specified, the monitoring operation is stopped after the
CPU module END processing.
(b) When Device is specified:
Word Device or Bit Device can be specified.
1) When Word Device is selected:
The monitoring operation is stopped when the current value of the specified
word device becomes the specified value.
A current value can be expressed in decimal digits, hexadecimal digits, 16-bit
integral numbers, 32-bit integral numbers, or real numbers.
2) When Bit Device is specified:
The monitoring operation is stopped when the execution status of the
specified bit device becomes the specified value.
Either the leading edge or the fall can be specified for execution condition.
Figure 6.34 Monitor stop condition screen