9
PARAMETERS
9.1 PLC Parameters
9.1.1 Basic model QCPU
9
- 13
9
P
a
ra
met
e
rs
10
Device
Exp
la
n
at
ion
11
CP
U
M
odu
le
P
ro
cessi
ng
Ti
m
e
12
P
roc
e
d
ure
f
or W
rit
in
g
P
rog
ra
m t
o CP
U Mo
du
le
A
p
pe
nd
ic
e
s
In
de
x
(11)Multiple CPU setting
Make the settings to configure a multiple CPU system.
Figure 9.11 Multiple CPU setting
Table9.11 Multiple CPU setting list
Item
Parameter No.
Description
Setting range
Default value
Reference
Number of PLC
0E00
H
Set the number of CPU modules
used by the multiple CPU
system.
1 to 3 modules
1 module
Refer to QCPU
User's Manual
(Multiple CPU
System).
Operation mode
0E01
H
Set the multiple CPU system
operation to be performed when
the CPU module No. 2 or No. 3
results in a stop error.
When the CPU No. 1 results in a
stop error, the multiple CPU
system stops. (Fixed)
Stop/Do not stop all CPUs at
error of CPU No. n
Stop all CPUs at
error of CPU No. n
I/O sharing
when using
Multiple
CPUs
All CPUs
can read all
inputs
0E04
H
Set whether the input status of
the input module or intelligent
function module controlled by
the other CPU will be imported
or not.
Do not import non-group input
status/Import non-group input
status
Do not import non-
group input status
All CPUs
can read all
outputs
Set whether the output status of
the output module controlled by
the other CPU will be imported
or not.
Do not import non-group output
status/Import non-group output
status
Do not import non-
group output status
Refresh setting
E002
H
E003
H
Set the device and its number of
points to/from which data will be
written/read by auto refresh
between the CPU modules of the
multiple CPU system.
[CPU specific send range]
No.1: 0 to 320 (2 point units)
No.2, 3: 0 to 2048 (2 point units)
per module
Max. 4416/system
No setting
[PLC side device]
B,M,Y,D,R,ZR
The device points set in the
transmission range are
occupied, starting from the
specified device number.
• 16 points of B, M or Y are
occupied in the transmission
range of one point.
• 1 point of D, W, R or ZR is
occupied in the transmission
range of one point.