6
- 72
6.11 Monitor Function
6.11.4 Executional conditioned device test
6
FUNCTIONS
(d) Checking executional conditioned device test settings
Select [Online] [Debug] [Executional conditioned device test] [Check/
disable executional conditioned device test] in GX Developer.
Remark
1. For the operation method of checking or disabling executional conditioned
device test settings, refer to the following manual.
GX Developer Operating Manual
2. Usage of the Executional conditioned device test can also be checked in the
special register (SD840). (
(e) When executional conditioned device test settings cannot be registered or
disabled
In the following cases, executional conditioned device test setting cannot be
registered or disabled.
When multiple settings are to be registered, all settings cannot be registered if any
of the settings applies to the cases below.
1) When executional conditioned device test settings cannot be registered
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• The number of registered executional conditioned device test settings
exceeds 32.
2) When executional conditioned device test settings cannot be disabled
• Specified program does not exist.
• Specified step does not exist.
• Specified device does not exist.
• No executional conditioned device test setting has been registered.
Figure 6.46 Screen for checking executional conditioned device test settings