6
- 40
6.8 Error Time Output Mode Setting
6
FUNCTIONS
6.8 Error Time Output Mode Setting
(1) Error time Output Mode Setting
The error time output mode setting is to set whether the output to the Q series
corresponding output module, I/O combined module, intelligent function module or
interrupt module will be cleared or held when the CPU module results in a stop error.
(2) Error time Output Mode Setting
Make the error time output mode setting in the I/O assignment setting of the PLC
parameter dialog box.
1) Make I/O assignment.
2) Select the
button.
3) Choose "Clear" or "Hold" for the slot to which the error time output mode is set.
(The default is "Clear".)
(3) Precautions
The error time output mode setting is made valid when:
• When the PLC is powered OFF and then ON
• When the CPU module's RESET switch is set to neutral position
Failure to perform either operation after changing the error time output mode setting
will result in "PARAMETER ERROR (error code: 3000)".
Figure 6.24 Error time output mode setting sequence
Detailed setting
3) Error time output mode
Select "Clear" or "Hold".
1) Make I/O assignment.
2) Select Detailed setting.